This is the performance index of AVIC version 1.3 water-cooled container. If your product is from other manufacturers or versions, it may differ slightly from this parameter. This parameter is for reference only.
Table 1: System performance metrics
No. | Name | Indicator | Remarks |
Environmental indicators | |||
1 | Operating temperature | -25~40℃ | Outdoor |
Operating temperature | 25~40℃ | Indoor (controllable temperature range by adjusting the fan) | |
2 | Working humidity | 10~90% | |
3 | Storage temperature | -35~70℃ | |
4 | Storage humidity | 5~95% | |
5 | Altitude | <2000m | |
Container technical indicators | |||
1 | Dimensions (mm) | 6058*2438|*2896 | |
2 | Miner capacity | 210 S19 Hydro series miners | |
3 | Box certification | Certified by the China classification society | |
4 | safety certificate | NFPA 79:2021 | |
5 | Running power | 1047~1050 | Excluding cooling tower power consumption |
6 | Input voltage and power | 415V±5%/60Hz | |
7 | Shipping weight | 8t | Without miners and coolant |
8 | Running weight | 12t | Contains miners and coolant |
9 | Main switch capacity of power distribution cabinet (A) | 1200 | The container contains two power distribution cabinets, each with a 1250A main switch |
10 | Rated current (A) | 952 | The rated current of each power distribution cabinet in the container |
11 | Standard power (kW) | 1047 | Cooling tower power consumption not included |
12 | Maximum power (kW) | 1050 | Cooling tower power consumption not included |
13 | Rated current of single unit (A) | 10 | The container contains two power distribution cabinets, each with a 1250A main switch |
14 | External interface (cooling tower) | DN125(GB/T 9119-2010 PN16 DN125) | |
15 | External interface (heating & board exchange interface) | DN100(GB/T 9119-2010 PN16 DN100) | |
16 | Flow (m³/h) | >85 | |
Cooling tower technical indicators | |||
1 | Type | Dry and wet combined cooling tower | |
2 | Dimensions (L*W*H) (mm) | 5800*2240*4200 | |
3 | Heat dissipation capacity (kW) | 1000 | |
4 | Running water temperature | 35℃±1℃ | @Wet bulb temperature=28℃ |
5 | Box certification | No | |
6 | Safety certificate | NFPA 79:2021 | |
7 | Operating power (kW) | 14~28 | |
8 | Shipping weight | 5 | |
9 | Running weight | 9 | |
10 | External interface (container) | DN125(GB/T 9119-2010 PN16 DN125) | |
11 | Water supply pipe interface | DN40(internal thread) | |
12 | Drain pipe interface | DN65(internal thread) | |
13 | Noise@25℃, 16m | 70dBA | |
14 | Water Consumption | 1~1.5m³/h |
Dear Customers,
Hello everyone, as China is about to usher in the Spring Festival, international logistics will be suspended. Zeus Mining is scheduled to stop shipping on January 18, 2025, and start the Spring Festival holiday from January 21 to February 4, 2025 (GMT+8). Pre-sales and after-sales service will reply to the information on February 5, 2025, and shipping will resume on February 8, 2025. Thank you for your support and trust in 2024. In 2025 and the future, we will bring better products and services to our friends.