Note: This is the water-cooled container parameter of the AVIC 1.3 version. If your product is from other manufacturers or versions, it may differ slightly from this parameter. This parameter is for reference only.
AntSpace HK3 V2 valve and pressure gauge function summary table | |||
No. | Name | Function | State |
1. | 1# ball valve | Valve for drain | Normally closed |
2. | 2# ball valve | Main line drain valve | Normally closed |
3. | 3# ball valve | Main line drain valve | Normally closed |
4. | 4# ball valve | Safety valve, when the safety valve fails, the valve can be closed for inspection. | Closed when pressed, the rest usually are open. |
5. | 5# ball valve | The valve at the front of the rehydration filter, closes this valve when the filter is overhauled. | Normally open |
6. | 6# ball valve | Open the water tank refill valve to refill the inside of the water tank. | Normally closed |
7. | 7# ball valve | Internal system rehydration valve in the pipeline; open this valve to refill the system. | Normally open |
8. | 8# ball valve | The water tank is connected to the system valve, open this valve, and the water tank is connected to the internal system of the pipeline and can be automatically replenished or discharged. | Normally open |
9. | 9# ball valve | The liquid replenishment inlet of the whole system and the liquid discharge outlet of the water tank. Open this valve to replenish the external liquid into the system/water tank; open this valve when the liquid is discharged, and the liquid inside the water tank will be discharged. | Normally closed |
10. | 10# ball valve | Expansion tank valve, close this valve when overhauling the expansion tank. | Closed when pressed, the rest usually are open. |
11. | 11# ball valve | The exhaust valve is at the top of the degassing tank; close this valve when overhauling the exhaust valve here. | Normally open |
12. | 12# ball valve | Exhaust valve, close this valve when overhauling the exhaust valve here. | Normally open |
13. | 13# ball valve | External Y-strainer valve, open when overhauling the filter and draining. | Normally closed |
14. | 1# welded butterfly valve | Bypass valve, open when the ambient temperature is low to allow internal circulation. | Normally closed |
15. | 2# welded butterfly valve | The valve of the left water distributor of the liquid return cooperates with the 4# welded butterfly valve to isolate the left water distributor assembly. | Normally open |
16. | 3# welded butterfly valve | The valve on the right side of the water separator for the return liquid cooperates with the 5# welded butterfly valve to isolate the left side water separator assembly. | Normally open |
17. | 4# welded butterfly valve | The valve of the left water distributor of the liquid supply cooperates with the 2# welded butterfly valve to isolate the left water distributor assembly. | Normally open |
18. | 5# welded butterfly valve | The valve of the right water distributor of the liquid supply is matched with the 3# welded butterfly valve to isolate the left water distributor assembly. | Normally open |
19. | 6# welded butterfly valve | Container liquid supply valve, closed when moving and transporting, independent water-cooled container system, can cooperate with 8# welded butterfly valve to maintain the filter, the system does not need to discharge a lot of liquid. | Normally open |
20. | 7# welded butterfly valve | Container liquid return valve, closed when moving and transporting, independent water-cooled container system. | Normally open |
21. | 8# welded butterfly valve | Cooling tower liquid supply valve, closed when moving and transporting, independent cooling tower, can cooperate with 6# welded butterfly valve to maintain the filter, the system does not need to discharge a lot of liquid. | Normally open |
22. | 9# welded butterfly valve | Cooling tower liquid return valve, closed when moving and transporting, independent cooling tower. | Normally open |
23. | 1# pressure gauge | The pump suction pressure gauge can judge whether the pump suction pressure (≥0.1MPa) is normal and can check whether the pump suction pressure sensor is normal. | / |
24. | 2# pressure gauge | The outlet pressure gauge of the pump, together with the 1# pressure gauge, can analyze whether the pump's operating conditions are consistent with the design conditions (the difference is the pump head at this time). | / |
25. | 3# pressure gauge | The pressure gauge of the main liquid supply line cooperates with the 2# pressure gauge to analyze whether the outlet pressure of the water pump is normal and whether there is any fault in the system. | / |
26. | 4# pressure gauge | The pressure gauge of the left branch pipe of the liquid supply and the 6# pressure gauge can analyze whether the flow resistance of the left water distributor assembly is normal. | / |
27. | 5# pressure gauge | The pressure gauge of the right branch pipe of the liquid supply and the 7# pressure gauge can analyze whether the flow resistance of the right water distributor assembly is normal. | / |
28. | 6# pressure gauge | The pressure gauge of the left branch pipe of the liquid supply and the 4# pressure gauge can analyze whether the flow resistance of the left water distributor assembly is normal. | / |
29. | 7# pressure gauge | The pressure gauge of the right branch pipe of the liquid supply and the 5# pressure gauge can analyze whether the flow resistance of the right water distributor assembly is normal. | / |