Notes for regular inspection of AntSpace HK3 V2 container water tank

When we are doing a regular inspection of the water tank of the AntSpace HK3 V2 container, the following points need to be paid attention to:

1. Pipeline leakage maintenance

The pipe network should be checked for leak-proof liquid when the equipment has been running for half a year. If any leakage or leakage is found, it should be shut down immediately for maintenance. For maintenance, stop the operation of the load device at the user end first, and then stop the unit's operation for repair. At the same time, after the leak detection is completed, pay attention to replenishing the system.

2. System sewage

After the system and the water tank have been running for two years, there may be some sundries in the system pipeline, and the system should be drained in time.

Sewage steps:

1) Find the positions of No.1, No.2, No.3, and No.9 ball valves (as shown in the figure below);

container ball valve position.jpg 

2) Connect the drain hose to the No.2 ball valve and No.3 ball valve, and use the hose clamp to fasten it; lead the hose to the outside of the unit, open the No.1-3 ball valve and No.9 ball valve, and the system can be sewage.

3. Check the liquid level of the water tank

The system monitors the liquid level of two water tanks (in the container and the cooling tower). When the liquid level in the water tank is lower than the required value, the system's touch screen will give an audible and visual alarm to indicate that the liquid level in the water tank is low. The fault should be checked and replenished liquid in time, but even if the water tank level is not alarmed, it should be checked regularly: the water tank level in the container must be checked once a week after the stable operation. If the water tank does not reach 2/3, it must be replenished in time. The liquid level of the cooling tower water tank must be checked once a day, and no water stop is allowed (unless the dry cooling mode is used in winter, at which time the water inside the cooling tower needs to be drained).

containers and cooling tower water tanks.jpg 

Note: This is the water-cooled container parameter of the AVIC 1.3 version. If your product is from other manufacturers or versions, it may differ slightly from this parameter. This parameter is for reference only.

0
About products purchase, please contact our sales manager:
[email protected]

About miner repair and after-sale issues, please contact the repair manager email:
[email protected]

For business cooperation, please contact:
[email protected]

COMPLAINTS & SUGGESTIONS
If you have any dissatisfaction during the transaction or have valuable suggestions for us, please contact us via this email address:
[email protected]
Attention!

Recently, many companies claiming to be mining companies imitate us and say that they are related to us, or that they are our branch companies, which has caused customers to be deceived. Please be careful not to believe any impostors, please check our correct contact information and beware of being deceived getting scammed, and losing money.
please check our right contact way: Here

CLOSE